0-100mA/0-1A/0-500mA Large current signal output isolators(output power <5W)
If need >5W,please check our DIN11D IAP series.
Features:
>> Optical Isolation
>> Accuracy grade: 0.1/0.2/0.5. Factory calibrated, the user can use directly
>> Auxiliary power supply: 5V/12V/15V/24VDC or 220VAC (± 10%)
>> One standard signal input: 0-5V / 0-10V/1-5V, 0-10mA / 0-20mA/4-20mA
>> One standard output signal: 0-100mA/0-500mA/0-1A current signal or 0~1V(max 1A)/0~10V(max 500mA) voltage signal
>> High linearity (nonlinearity <0.2%)
>> DIN35 rail mounting
>> Size: 106.7x79.0x25.0mm
>> Strong anti-electromagnetic interference and high-frequency signal interference capability
Application:
>> Analog signal data isolation, collection and transformation
>> Isolated 4-20mA or 0-20mA signal transmission
>> Signal isolation and conversion of industrial site
>> Long-term signal transfer without distortion
>> Instrument signal transceiver
>> Power monitoring, medical equipment isolation
Product Listing:
DIN11L IAP - V(A)□ - P□ – V(I)□
Input Signal | Power Supply | Output Signal |
Voltage | Code | Current | Code | Power | Code | Current | Code | Voltage | Code |
0-5V | V1 | 0-1mA | A1 | 24VDC | P1 | 0-20ma | A3 | 0~5V | V1 |
0-10V | V2 | 0-10mA | A2 | 12VDC | P2 | 4-20ma | A4 | 0-10V | V2 |
0-75mV | V3 | 0-20ma | A3 | 5VDC | P3 | user-defined | Az | 1-5V | V6 |
0-2.5 | V4 | 4-20mA | A4 | 15VDC | P4 | | | user-defined | Vz |
user-defined | Vz | user-defined | Az | | | | | | |
Samples:
1: Input: 4-20mA Power Supply:24V Output: 0-10V ,20 ohm Type No.: DIN11L IAP A4-P1-V2(20 ohm)
2: Input: 4-20mA Power Supply: 24V Output: 0-500mA,20 ohm Type No.: DIN11L IAP V4-P1-Az(Az:0-500mA,20 ohm)
Note:when you order,please note your output load or output current.If out power>5W,please choose our another series: